RETAIL PRICE: R12,999-00
Key Features:
- Zero (0ms) transfer time to protect mission-critical loads such as servers and ATMs.
- High PV input voltage range
- Removable LCD control module with multiple communications
- Selectable high power charging current
- Built-in Wi-Fi for mobile monitoring (App is available)
- Configurable AC/Solar input priority via LCD setting
- Reserved communication port for BMS (RS485 or CAN-BUS)
- Parallel operation up to 9 units
- 6000W Max PV array
| SALVARE FIVE – 5KW HYBRID INVERTER SPECIFICATIONS | |
| Voltronic Model | Axpert King II-5000-48 |
| Rated Power | 5000VA/5000W |
| Parallel Capacity | Up to 9 Units |
| GRID INPUT | |
| Voltage | 230VAC |
| Selectable Voltage Range | 110 – 280VAC |
| Frequency Range | 50Hz/60Hz (Auto sensing) |
| Power Factor | ≥ 0.98 @ Nominal Voltage (100% Load) |
| THDi | ≤ 10% |
| LOAD OUTPUT | |
| Frequency Range (Synchronised Range) | 46~54 Hz or 56~64 Hz |
| Frequency Range (Battery Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
| Harmonic Distortion | ≦3 % THD (Linear Load); ≦ 5 % THD (Non-linear Load) |
| Transfer Time | AC Mode to Batt. Mode – 0ms Inverter to Bypass – 4ms |
| Waveform | Pure Sine Wave |
| EFFICIENCY | |
| Line Mode | 94% |
| ECO Mode | 98% |
| Battery Mode | 92% |
| BATTERY | |
| Battery Voltage | 40-62 VDC |
| Floating Charge Voltage | 54 VDC |
| Overcharge Protection | 62 VDC |
| SOLARCHARGER AND AC CHARGER | |
| Solar Charger Type | MPPT |
| Maximum PV Array Power | 6000W |
| MPP Range @ Operating Voltage | 120-450VDC |
| Maximum PV Array Open Circuit Voltage | 500VDC |
| Maximum Solar Charge Current | 100A |
| Maximum AC Charge Current | 100A |
| PHYSICAL | |
| Dimension, D X W x H (mm) | 138.4 x 298 x 467.6 |
| Net Weight (kg) | 12 |
| Communication Interface | RS232, USB, DRY CONTACT, WI-FI, RS485, CAN |
| OPERATING ENVIRONMENT | |
| Humidity | 5% – 95% Relative Humidity (non-Condensing) |
| Operating Temperature | -10°C to 50°C |
| Storage Temperature | -15°C to 60°C |